The modularization of UPS is to divide the entire UPS into several parts according to its main functional components, such as power conversion, battery system, intelligent management and communication, providing high efficiency and overload capability. +Power is a true modular UPS system that can be easily expanded UPS capacity, up to 300KW. Modular design is applied to power modules, STS modules and battery modules. Modular design makes maintenance and replacement easier and reduces mean time to repair (MTTR)
N+1 or N+R1 parallel redundant application design increases system flexibility, stability and safety
High-efficiency double conversion online uninterruptible power supply system
Output power factor 1.0
Modular design, easy to expand , update and maintain, which can reduce after-sales maintenance costs
STS modules use redundant power supplies to achieve highly reliable operation
Adjustable charging current
Adjustable number of battery cells
Powerful overload capability
LCD graphics Design, the display is more direct and clear
Optional 10 touchable colorful LCD screen
Industrial application protection
Experimental instruments and equipment
Office automation
Communication network management center
Small data computer room
Power supply protection for important institutions such as transportation, electricity, medical, and stadium
Model | Power | Size (Width * depth * height) | Weight (kg) |
GM33-90K- | 90KW | 600*110*1475mm | 675 |
GM33-120K- | 120KW | 600*1100*2010mm | 932 |
GM33-180K- | 180KW | 600*1100*1475mm | 335 |
GM33-200K- | 200KW | 600*1100*2010mm | 611 |
GM33-210K- | 210KW | 600*1100*2010mm | 549 |
GM33-300K- | 300KW | 600*1100*2010mm | 620 |
GM33-600K- | 600KW | 600*1100*2010mm | 1300 |
*Current specifications and dimensions are subject to change without prior notice。
Input | |||||||
voltage range | 305-478VAC | ||||||
Rated voltage | 3X380/400/415VAC | ||||||
Frequency Range | 40~70HZ | ||||||
Rated frequency | 50/60HZ | ||||||
Power Factor | >0.99 | ||||||
Harmonic Distortion (THDI) | <3% | ||||||
Output | |||||||
Rated frequency | 50/60HZ | ||||||
Overload capacity | 1 hour 110%, 10 minutes 125%, 1 minute 150%, 200 seconds > 150% | ||||||
Voltage adjust | ≤±1% | ||||||
Rated voltage | 3X380/400/415 VAC(3Ph+N) | ||||||
Efficiency | 94.50% | ||||||
Harmonic Distortion (THDI) | ≤2% | ||||||
Frequency range (synchronization range) | 46`64HZ | ||||||
Batteries and chargers | |||||||
Float charge voltage | 2.25V/CELL | ||||||
Increase charging voltage | 2.35V/CELL | ||||||
Maximum charging current | 8A | ||||||
maximum voltage | +/-240v (12vx40pcs) | ||||||
Rated voltage | +/-216v (12vx36pcs) | ||||||
Temperature compensation | yes | ||||||
lowest voltage | +/-192v (12vx32pcs) | ||||||
Environment | |||||||
Altitude | <1000m | ||||||
IP class | IP20 | ||||||
Operating temperature | 0~40°C | ||||||
Working humidity | 0~95% | ||||||
Management | |||||||
Optional, SNMP | Power management from SNMP manager and web browser | ||||||
Smart RS-232/USB | Support windows2000/2003/ MAC | ||||||
Standard | |||||||
Safety verification | IEC/EN60950-1; IEC/EN62040-1 |